General information

DALI Product ID5968
Product NameRAPIX DALI-2 Two Channel DIN Relay
Brand NameOzuno
StatusCertified: DALI-2
Product Part NumberDGOZ-DINRLY-12A-02
GTIN9355691000459
Bus unit configuration-

External link to product

https://ozuno.com/product/rapix-dali-2-two-channel-din-relay-12-amp/

Testing

Test conditions240V, 50Hz supply. Ambient temperature 25C. Ozuno OZDC36C500PD LED driver load with 36V Inlite Super Hero XP LL-060-30-36 LED lamp connected to each channel.
Test typeFull
Family reference product ID-
DALI test sequence software version2.5.0.0

Technical

Bus current consumption

Maximum current consumed from the bus power supply. If no value shown, 2mA is required.

1.9
Guaranteed supply current

Current that this bus power supply can provide. Total must be sufficient to provide the total "bus current consumption" of all devices.

0
Maximum supply current

Highest current that this bus power supply may provide. Total must not exceed 250mA.

0

Hardware/firmware information

If multiple versions exist then contact the manufacturer for details of the older versions.

Hardware version1.0
Firmware version2.0, 2.1

Description

These DALI one and two channel DIN mount Relays are designed for on/off switching of up to 12 Amps of lighting load via DALI commands issued on a connected DALI line. Each relay channel is capable of switching 12 A of LED, fluorescent, incandescent and HID lighting loads for ac line voltages of 100 – 240 V, making it suitable for a wide range of commercial and industrial building applications. Relay cable termination uses high quality rising cage clamp style screw terminals, and is suitable for terminating 1.5 mm2 or 2.5 mm2 cables (ac supply cables, switched load cables and DALI Line cables). To maximise contact life, the relay unit includes zero cross switching which ensures that for switch-on, the relay contacts are closed at the ac voltage zero-crossing point. Perfect for all Commercial & Industrial buildings, Education Facilities, Health care facilities, Hotels, Warehouses, and Residential Homes.

DALI parts and versions

1012.0
1022.0
2082.0

Product properties

LED drivers, ballasts, ECGs, etc.

Maximum current consumed from the bus power supply. If no value shown, 2mA is required.

“Other properties” do not imply certification to such standards.