DALI Product ID | 3255 |
Product Name | KNX DALI-Gateway Basic REG-K/2/16/64 |
Brand Name | Schneider Electric |
Status | Certified: DALI-2 |
Product Part Number | MTN6725-0004 |
GTIN | 3606489484057 |
Bus unit configuration | - |
https://www.se.com/ww/en/product/MTN6725-0004/knx-dali-gateway-basic-reg-k-2-16-64/?range=1424-knx
Test conditions | ProbitLab2 DALI Tester, ProbitBench V4.2.7.0, Hewlett Packard 34401A Multimeter, Agilent DSOX2004A Oszilloscope |
Test type | Full |
Family reference product ID | - |
DALI test sequence software version | 2.1.1.0 |
Bus current consumption Maximum current consumed from the bus power supply. If no value shown, 2mA is required. | |
Guaranteed supply current Current that this bus power supply can provide. Total must be sufficient to provide the total "bus current consumption" of all devices. | 128 |
Maximum supply current Highest current that this bus power supply may provide. Total must not exceed 250mA. | 250 |
If multiple versions exist then contact the manufacturer for details of the older versions.
Hardware version | 0B |
Firmware version | 0.2.6 |
KNX DALI Gateway
The KNX DALI Gateway connects the KNX bus to 2 DALI outputs. The gateway is a category I DALI control device with an integrated DALI power supply for the ECGs. The device is a Single-Master Controller according to EN 62386 ed/1 and ed/2. It is able to control DALI ECGs ed/1 and ed/2 -also mixed- but according to single-master controller it cannot support DALI-2 sensors like movement- and presence detectors, switches etc. For each DALI output, it supports the switching and dimming of up to 64 ECGs in 16 groups and the control of up to 16 scenes.
101 | 2.0 |
103 | 2.0 |